EOLO

EOLO 2 loop addressed digital panel

Hardware Features

  • 16 bit microprocessor analog unit
  • 2 digital protocol addressed analog loops with open or closed configuration
  • 240 detectors/modules per loop.
  • 40×2 character LCD display with back-light function
  • Touch keypad with 25 function keys
  • 2 open or closed loops
  • Loop short circuit protection.
  • 17 frontpanel LEDS
  • 1 supervised sounder output (24Vdc 1A)
  • 1 supervised output to trigger the fire alarm signal devices or the activation of the extinguisher devices
  • 1 fault relay output with floating contacts -1A 30Vdc 120 V ac
  • 1 excluded sensors/modules/areas relay output with floating contacts -1A 30Vdc 120 V ac
  • 1 technological relay output with floating contacts -1A 30Vdc 120 V ac
  • 1 RS 485 serial line for connection to remote panels and printer
  • 1 RS 232C serial line for centralization, remote management and remote programming with CEI 79/5, 79/6 protocol)
  • 1 alarm relay output with floating contract output
  • Programming data stored on non volatile EEPROM memories n. 2 17aH capacity accumulators with temperature controlled battery charger
  • Warning signals for:
  1. 230 Vac power supply absence
  2. Battery absence
  3. Low battery
  4. Faulty battery charger
  • Auxiliary power output 24 Vdc 2.5 monitored and protected against short circuits for external loads
  • Management of additional conventional line via FDVMCZ100 module
  • Power consumption when idle 300 mA at 12Vdc (430mA on primary 230Vac)
  • Dimensions: 450x410x130 mm
  • Power supply: 230Vac/27Vdc 5.6A

Functional characteristics

  • Division in up to 32 detection areas
  • 32 logic functions
  • Historically archive of the last 385 events
  • Automatic loop devices discovery
  • Management of various types of detectors and analog modules:
  1. Optical,Thermal and mixed detectors
  2. Input modules
  3. Output modules
  4. Addressed buttons
  5. Addressed analog sounders
  • Customised programming of phrases for each input
  • 1 programming password
  • 1 Maintenance password
  • Technological functionality
  • Local or remote programming using local Win SW via serial line or LAN/WAN network
  • Management of gas detection

Reference Standards

  • Product certified to EN54-2 and EN54-4
  • Certified N° 1293-CPD-0154 standards CE Marking (EMC low voltage directive